product quick search

  homeproducts datasheets |  applications case studies  support  |  contact us

 

Other signal Conditioners
 
Signal Conditioner for S/G Transducer

Potentiometeric  Signal Conditioner

Strain Amplifier Signal conditioner
 

just  

 arrived

AGMPL Material Testing Machines catalogue.
Get your copy TODAY !!!



 

  LVDT Instrumentation
Signal Conditioners Cards / Modules

AC LVDT Signal Conditioner Card  - AC 301, AC 302 

  datasheet


AG Measurematics
offers a family of signal conditioning products designed specifically for producing usable outputs proportional to relative motion between the core rod and housing of an AC LVDT.

AC 301
is a single channel signal conditioner card. It accepts AC LVDT signals of most of the standard makes. It to provide a bipolar voltage output which can be adjusted up to +/-10V for full or part stroke of an LVDT.

AC 302
has similar specifications as AC 301 except that it also provides a 4 to 20mA output.
 

AC LVDT Signal Conditioner Module  - AI 301, AI 302   


AI 301
is a signal conditioner module, which incorporates AC 301 along with a mains operated power supply. It is housed in a IP65     cast aluminum enclosure. It can also be used in hostile shop floor or outdoor applications.

AI 302
is a signal conditioner module, which incorporates AC 302 along with a mains operated power supply. It is housed in a IP65 cast aluminum enclosure.

Separate Power supply card and transformer are also available as a set to be used with AC 301 or AC 302 Cards

Specifications  
LVDT acceptable 3,4,5 or 6 wire type
LVDT excitation Standard--Factory set at 2V rms, 2kHz, sine-wave User specific: up to 5v rms, 500Hz to 5kHz, sine-wave
AC amplifier gain 2 to 20, site adjustable through card mounted screwdriver control
Phase adjustment range ± 20 degree lag or lead site adjustable through card mounted screwdriver control
Low pass filter frequency 10, 100 Hz, site adjustable through card mounted jumpers
Zero adjustment range Site adjustable through card mounted screwdriver control
Maximum output range ± 10 V into 2K load
Input & output termination Screw terminals
Dimensions AC 301, AC302,-100x160; AI 301, AI 302-210X130X85 mm
Power source AC 301, AC302 ±15V DC; AI 301,AI 302-230V,+10%, 50Hz

LVDT Signal Conditioner Module AM321

The AM321 module is LVDT signal conditioner which conditions the LVDT signal and provides an analogue output proportional to LVDT core displacement. Front panel controls include PHASE- to adjust the amplifier according to phase difference between primary and secondary voltage. SPAN - to adjust the amplifier output corresponding to full stroke range of LVDT.  ZERO- to set amplifier output to zero for initial core position. Incorporated on the board are  sine wave oscillator for transducer excitation, amplifier, demodulator and low pass filters. Analogue output of signal conditioners is terminated on the 64 pin EURO connector along with power supply inputs and transducer connection. Eight such signal conditioner modules can be housed in an AH391 Cabinet.

Specifications
LVDT Excitation Adjustable from 0.5 to 3.0 Vrms; 2 Khz; Factory set at 2.00 Vrms
LVDT Acceptable 3, 4, 5, or 6 wire type
Amplifier Gain 2 to 20 adjustable
Phase Sensitive Demodulator Adjustable phase
Low Pass Filter ± 10 / 100 Hz jumper selectable
Output Offset ± 10 V (  into 2K Load)
Power Supply/ Sensors/ Output Termination 64 pin Euro connector.
Type: DIN 41612
Dimensions 100 x 60 mm
Panel Width 30 mm
Power Supply ± 15 V DC nominal, 150 mA
 


 

 
terms of use  | copyright notice   | sitemap  | Optimized for 800 x 600 screen resolution 